Xue, H. (author), Popov, M. (author)
Large transient overvoltages are normally caused by vacuum circuit breaker (VCB) switching operation during disconnection of induction motors. In this paper VCBs, cables, generators, busbars, induction motors and surge arresters are modeled by making use of ATP-EMTP. Switching transient overvoltages of four typical induction motors are analyzed...