Alf Peter Elg
Please Note
4 records found
1
The National Metrology Institute (NMI) of The Netherlands (VSL) developed a new 1200-kV reference measuring system for on-site calibration of lightning impulse (LI) voltage measuring systems. Improvement of the low-voltage grounding loop and triaxial signal transmission reduced oscillation ripples and enhanced the shielding of environmental high-frequency interference. Calibration and measurement capabilities are realized in the test voltage (Ut), front time (T1), and time to half-value (T2) with uncertainties of 0.7%, 3.0%, and 1.5%, respectively, up to 600 kV and 1.2%, 5.0%, and 3.0%, respectively, up to 1200 kV for direct comparison calibration. With additional linearity experiments, VSL is now able to provide LI voltage calibrations on-site up to 3000 kV. The VSL system was used as the reference for calibration and tuning of a 4000-kV LI divider to improve its accuracy performance. A measurement campaign was held to compare different LI measuring systems and research the linearity of the measuring system up to 3000 kV. The comparison results confirmed the good performance of the VSL 1200-kV reference measuring system and also indicated that the 4000-kV measuring system was improved after calibration and tuning with the VSL reference system.
The insulation condition of HVDC grids consisting of cable systems, GIS, and converters should be monitored by partial discharge (PD) analysers using artificial intelligence (AI) tools for efficient insulation diagnosis. Although there are many experiences of PD monitoring solutions developed for the supervision of the insulation condition of HVAC grids using PD analysers, there are no standardised requirements for their qualification available yet. The international technical specification TS IEC 62478 provides general rules for PD measurements using electromagnetic methods but does not define performance requirements for qualification tests. HVDC and HVAC PD analysers must be tested by unambiguous test procedures. This paper compiles experiences of using PD analysers with HFCT sensors in HVAC grids (cable systems, GIS, and AIS) to define a qualification procedure for HVAC systems. This procedure is applicable to HVDC grids (cable systems, GIS, AIS, and converters) because the particularities related to the insulation behaviour under HVDC voltage are also considered. Representative PD sources are discussed in HVAC and HVDC positive and negative polarity. The PD pulse trend of representative insulation defects in HVDC cable systems is quite different from that of HVAC grids. Special attention should be paid to the acquisition of PD signals in HVDC grids since few pulses appear in solid insulations, mainly during voltage changes (polarity reversals or surges), but rarely in continuous operation with constant direct voltage. A synthetic PD simulator has been developed to reproduce trains of PD pulses or noise signals, similar to those that can appear in the power network. A set of three functionality tests has been developed for qualification of the diagnostic capabilities of PD analysers working up to 30 MHz addressed to HVDC or HVAC grids: (1) PD recognition test, (2) PD clustering test, and (3) PD location test. This qualification procedure has been validated by means of a round-robin test performed by five research institutes (RISE, FFII, TUDelft, TAU, and UPM) using commercial and in-development AI PD recognition and clustering tools to demonstrate its robustness and applicability. Applying this qualification procedure, two PD methods for electrical detection and prevention of insulation defects have been approved, one for HVAC and the other for HVDC grids.
On-site partial discharge (PD) measurements have turned out to be a very efficient technique for determining the insulation condition in high-voltage electrical grids (AIS, cable systems, GIS, HVDC converters, etc.); however, there is not any standardised procedure for determining the performances of PD measuring systems. In on-line and on-site PD measurements, high-frequency current transformers (HFCTs) are commonly used as sensors as they allow for monitoring over long distances in high-voltage installations. To ensure the required performances, a metrological qualification of the PD analysers by applying an evaluation procedure is necessary. A novel evaluation procedure was established to specify the quantities to be measured (electrical charge and PD repetition rate) and to describe the evaluation tests considering the measured influence parameters: noise, charge amplitude, pulse width and time interval between consecutive pulses. This procedure was applied to different types of PD analysers used for off-line measurements, sporadic on-line measurements and continuous PD monitoring. The procedure was validated in a round-robin test involving two metrological institutes (RISE from Sweden and FFII from Spain) and three universities (TUDelft from the Netherlands, TAU from Finland and UPM from Spain). With this round-robin test, the effectiveness of the proposed qualification procedure for discriminating between efficient and inappropriate PD analysers was demonstrated. Furthermore, it was shown that the PD charge quantity can be properly determined for on-line measurements and continuous monitoring by integrating the pulse signals acquired with HFCT sensors. In this case, these sensors must have a flat frequency spectrum in the range between several tens of kHz and at least two tens of MHz, where the frequency pulse content is more significant. The proposed qualification procedure can be useful for improving the future versions of the technical specification TS IEC 62478 and the standard IEC 60270.
Society's increasing demand for electrical energy, along with the increased integration of remote renewable generation has driven transmission levels to ever higher voltages in order to maintain (or improve) grid efficiency. Consequently, high voltage testing and monitoring beyond voltage levels covered by presently available metrology infrastructures are needed to secure availability and quality of supply. Calibration services for Ultra-High Voltage Direct Current (UHVDC) presently are only available up to 1000 kV. There is a need to extend the DC calibration capabilities for voltage instrument transformers up to 1200 kV and for factory component testing capabilities up to 2000 kV. Also, methods for linear extension of lightning impulse calibration, for dielectric testing of UHV grid equipment, urgently need revision. Recent research has raised questions regarding the validity of the current linearity extension methods for voltages beyond 2500 kV. Furthermore, new methods for calibration are needed for the 0.2 class HVAC voltage instrument transformers for system voltages up to 1200 kV. The current methods used for determination of the voltage dependence are very time consuming, raising the need for methods allowing faster assessment. Finally, with new HVDC transmission grids and associated components, novel methods are needed for detection, classification and localisation of partial discharge (PD) under DC stress. The industry needs methods for reliable monitoring of critical components such as cables, for both HVAC and HVDC, and gas insulated substations (GIS), and techniques for addressing new challenges introduced by HVDC technologies, such as the ability to distinguish PD signals from switching transients in converters and other sources of noise.