PD measurement is a worldwide-accepted method for insulation diagnosis and a required part of the acceptance testing for many HV assets. To facilitate PD measurements different techniques/methods have been developed and they are in use for laboratory and on-site applications. All ...
In searching process for new, advanced technologies which could be applied for on-site diagnostics of machine insulation this paper discuses the application of damped AC voltages to detect and to analyze the PD processes. Based on laboratory investigation on a full scale stator i ...
Performing on-site non-destructive testing and diagnosis of HV power cables is becoming an important issue to determine the actual condition of the cable systems and to determine the future performances. Therefore in this contribution based on field application of on-site testing ...
Diagnostics of HV power cables are playing an important role in the meaning of two aspects: 1) on-site diagnostic of new installation, where a commissioning test has to prove the absence of any defects in the cable insulation and accessories, after transportation and installation ...
Partial discharges (PD) diagnostics play an important role in insulation diagnosis of HV power cables all over the world. By application of such diagnostic it is possible to asses the quality of final product (cable) during factory test, during after-laying test or during service ...
This document describes application of statistical analysis to several diagnostic parameters obtained during on-site measurements on MV power cables. The goal of this analysis is to estimate statistical borders values for different diagnostic parameters related to PD phenomena fo ...
Water treeing is a phenomenon that is already known for more then 35 years and is one of the reasons for cable failures (polymeric cables) in the medium-voltage network. The final stage of water treeing is the formation of electrical trees on top of the water trees. Due to the fa ...
Knowledge rules for paper/oil insulated high voltage (HV) power cables are necessary to support asset management decision processes. For development of these knowledge rules investigation has been done into a diagnostic method, for integral condition assessment of paper/oil insul ...
Failure data together with the length and the ages of mass-insulated power cables the still in service of a Dutch utility are used as input for the statistical analysis. The choice of the appropriate distribution depends on the goodness of fit to the data. The fitted statistical ...
In this paper measuring results of partial discharges in power cable accessories are described. For the purpose of measuring simultaneously partial discharge activity in three or more accessories during an acceptance test, a wireless partial discharge detection system was develop ...
For advanced, non-destructive on-site condition monitoring of HV power cables up to 150kV by partial discharge detection and dielectric losses measurement it is necessary to energize the disconnected cable system. One of the methods available for this purpose is based on applying ...
The practical interest of power utilities regarding the maintenance and replacement policy of insulating systems such as cables, switchgear and transformers is often based on experiences knowledge and data from the past. The ages of components in the network are increasing and th ...
It is known that many failures of power transformers are related to aging effects of the on-load tap changer contacts. This paper discusses the recently developed analysis method for service aged power transformers. In particular, the effect of several aging stages of the tap cha ...
This contribution is focused on the application of laboratory dielectric losses measurements to the insulation of service aged oil-impregnated HV power cables. The goal is to investigate the dependence between the electrical and temperature stresses to impregnated paper insulatio ...
This paper introduces a new advanced partial discharge detection system for detecting partial discharge activity in the accessories of power cables during the acceptance test. The system consists of three autonomous PD measuring systems which communicate via a wireless communicat ...
Resistance measurements on power transformers are offline diagnostic methods that are performed without opening the transformer main tank. In case the power transformer is equipped with an on-load tap changer (OLTC), this resistance measurement can be used to find degradation and ...
Already existing knowledge about aging phenomenon in type insulated power cables as well as measuring criteria has been continuously improved during last 20-30 years. Nowadays many HV power circuit with paper insulation reach their end of service life time due to extensive deteri ...
Condition assessment of HV assets is one of the issues of asset management in power utility business. In particular, due to there importance in the transmission network is the knowledge about the starting conditions during after-laying as well as the actual condition of HV power ...
For advanced, non-destructive on-site condition monitoring of HV power cables up to 150 kV by partial discharge detection and dielectric losses measurement it is necessary to energize the disconnected cable system. One of the methods available for this purpose is based on applyin ...
This paper describes important aspects of PD diagnostics of distribution power cables. PD parameter were discussed under consideration of attenuation and dispersive effects of cable characteristics. Field experiences with PD diagnosis on PILC and XLPE cables by energizing with Da ...