Sensitivity analysis of design parameters for melting process of lauric acid in the vertically and horizontally oriented rectangular thermal storage units

Journal Article (2022)
Author(s)

Vahid Safari (University of Tehran)

Babak Kamkari (Azad Islamic University, Ulster University)

K. Hooman (TU Delft - Process and Energy)

J. M. Khodadadi (Auburn University)

Department
Process and Energy
Copyright
© 2022 Vahid Safari, Babak Kamkari, K. Hooman, J. M. Khodadadi
DOI related publication
https://doi.org/10.1016/j.energy.2022.124521
More Info
expand_more
Publication Year
2022
Language
English
Copyright
© 2022 Vahid Safari, Babak Kamkari, K. Hooman, J. M. Khodadadi
Department
Process and Energy
Volume number
255
Reuse Rights

Other than for strictly personal use, it is not permitted to download, forward or distribute the text or part of it, without the consent of the author(s) and/or copyright holder(s), unless the work is under an open content license such as Creative Commons.

Abstract

Widespread commercialization of PCM-based latent heat storage systems is limited by the low melting and solidification rates during the phase transition process. In this study, fins are used to enhance the phase change process. A parametric study is conducted to understand the effect of fins on the thermal performance of vertically- and horizontally-oriented rectangular storage tanks. Throughout simulations, the fin volume, and thereby the mass of PCM in the tank, were kept constant. It was observed that the horizontal enclosures can take advantage of the development of strong natural convection flow until near the end of the melting process, whereas with vertical counterparts the strength of the convection currents was diminished during the shrinkage stage. The results suggest that longer and thinner fins are more beneficial for enhancing the melting rate than shorter and thicker fins. It was concluded that for horizontal enclosures with fin lengths of 25 and 35 mm, increasing the number of fins does not necessarily shorten the melting time. The maximum melting time reduction compared to the 3-fin vertical enclosure with a fin length of 25 mm (chosen as our benchmark case) was 75.1% when nine 45-mm-long fins are used in a horizontal enclosure.