General Analysis of Vacuum Circuit Breaker Switching Overvoltages in Offshore Wind Farms

Journal Article (2016)
Author(s)

S.M. Ghafourian (The University of Manchester)

I. Arana (Dong Energy)

J. Holbøll (Technical University of Denmark (DTU))

T. Sørensen (Dong Energy)

Marjan Popov (TU Delft - Intelligent Electrical Power Grids)

V Terzija (The University of Manchester)

Research Group
Intelligent Electrical Power Grids
DOI related publication
https://doi.org/10.1109/TPWRD.2016.2556423 Final published version
More Info
expand_more
Publication Year
2016
Language
English
Research Group
Intelligent Electrical Power Grids
Issue number
5
Volume number
31
Pages (from-to)
2351-2359
Downloads counter
129

Abstract

Understanding mechanisms of switching transient overvoltages in modern electrical power systems is a necessity to ensure a proper design of power plants and switchgear and the required level of reliable and secure system operation. High fidelity plant modelling and accurate transient analysis is a prerequisite for understanding the mechanisms of how overvoltages are created and whether or not the voltage withstand capabilities of system components will be exceeded. This research is focused on switching overvoltages typical for an offshore wind farm power collection grid configuration that comprises vacuum circuit breakers (VCBs), cables and transformers. An in-depth understanding of the prestrike effects in VCBs is a prerequisite for studying switching transient overvoltages. In this paper, the impact of VCB parameters (e.g., stray capacitance and withstand voltage ability)and cable length on the transformer terminal voltage during closing operation was studied. A wind farm power collection system was modelled in ATP-EMTP environment. To validate the results obtained through computer simulation, field measurements from an actual system were used.