Investigation of the energetic and exergetic performance of hybrid rotary desiccant-vapor compression cooling systems using different refrigerants

Journal Article (2024)
Author(s)

K.N. Çerçi (Tarsus University, TU Delft - Heat Transformation Technology)

I.S. Oliveira Silva (TU Delft - Process and Energy, Universidade de Coimbra)

K. Hooman (TU Delft - Heat Transformation Technology)

Research Group
Heat Transformation Technology
DOI related publication
https://doi.org/10.1016/j.energy.2024.131732
More Info
expand_more
Publication Year
2024
Language
English
Research Group
Heat Transformation Technology
Bibliographical Note
Green Open Access added to TU Delft Institutional Repository 'You share, we take care!' - Taverne project https://www.openaccess.nl/en/you-share-we-take-care Otherwise as indicated in the copyright section: the publisher is the copyright holder of this work and the author uses the Dutch legislation to make this work public.@en
Volume number
302
Reuse Rights

Other than for strictly personal use, it is not permitted to download, forward or distribute the text or part of it, without the consent of the author(s) and/or copyright holder(s), unless the work is under an open content license such as Creative Commons.

Abstract

In this study, a desiccant-based hybrid cooling system supported by a vapor compression system and a heat recovery unit (rotary heat wheel) was analyzed from energetic and exergetic perspectives during the daily working hours of an office building in Istanbul to meet the desired comfort conditions. We focus on the impact of different refrigerants; namely R32, R1234yf, R290, R134a, R600a, R245fa, and R717, on hybrid rotary desiccant-vapor compression systems. While the highest electricity consumption was obtained in the system using R1234yf, the lowest electricity consumption was achieved with R717. However, with the effectiveness of the desiccant wheel, the best results were obtained for R1234yf with those pertinent to R717 at the other extreme. Considering the total electricity consumption of the system, the highest energetic and exergetic performance parameters were achieved with the use of R717 as the refrigerant. Compared to R1234yf, the daily average energetic performance parameters obtained with R717 increased by 22.3 % for COP
r, 21.8 % for COP
el, and 4.7 % for COP
th. Similarly, compared to R1234yf, the daily average exergetic performance parameters in R717 presented increases of 13.6 % for COP
x,el, 7.5 % for COP
x,th, and 8.1 % for η
x.

Files

1-s2.0-S0360544224015056-main.... (pdf)
(pdf | 8.64 Mb)
- Embargo expired in 24-11-2024
License info not available