Countermeasures of Zero-missing Phenomenon in (E)HV Cable Systems
H Khalilnezhad (TU Delft - Intelligent Electrical Power Grids)
M. Popov (TU Delft - Intelligent Electrical Power Grids)
L. Sluis (TU Delft - EEMS - General)
Jorrit A. Bos (TenneT TSO B.V.)
JPW de Jong (TenneT TSO B.V.)
A. Ametani (Doshisha University)
More Info
expand_more
Other than for strictly personal use, it is not permitted to download, forward or distribute the text or part of it, without the consent of the author(s) and/or copyright holder(s), unless the work is under an open content license such as Creative Commons.
Abstract
Zero-missing is a phenomenon in shunt compensated cable systems in which the current through the line breaker does not cross the zero point for several cycles. This paper deals with a thorough investigation on countermeasures of the zero-missing phenomenon in transmission systems and determines the requirements, benefits, and risks of applying each method. The effectiveness of countermeasures is studied on a simulated cable project with different cable lengths in an actual grid model of the Dutch 380 kV transmission system. Results are analyzed based on three criteria related to the IEC standards and the Dutch grid code. In addition, the switching sequence of circuit-breakers is specified to maximize the effectiveness of the countermeasures. A statistical switching analysis is performed for the insulation coordination study since the application of some countermeasures increases the probability of high transient switching overvoltages. Moreover, the closing variation threshold of circuit-breakers is calculated as a function of the circuit impedance and the shunt compensation degree.