Development of an MRI-Compatible Sub-Atmospheric Two-Phase Thermosyphon Loop
T. Kyriakos (TU Delft - Mechanical Engineering)
M.R. Serial – Mentor (TU Delft - Mechanical Engineering)
E. Zanetti – Mentor (TU Delft - Mechanical Engineering)
M. Dionísio – Mentor (TU Delft - Mechanical Engineering)
W.J. Hogendoorn – Graduation committee member (TU Delft - Mechanical Engineering)
More Info
expand_more
Other than for strictly personal use, it is not permitted to download, forward or distribute the text or part of it, without the consent of the author(s) and/or copyright holder(s), unless the work is under an open content license such as Creative Commons.
Abstract
Two-phase flow carries most of the heat in evaporators and condensers, yet its internal structure is hard to measure without disturbing it. Magnetic resonance imaging resolves liquid distribution and velocity inside an opaque pipe without contact, but every published two-phase MRI study uses air and water near atmo-
spheric pressure. Water and steam below atmospheric pressure, where the liquid is twelve thousand times denser than its vapor, have never been imaged.
This thesis covers the design, construction and operation of a thermosyphon loop built for that purpose. The loop is a closed circuit in which water boils, rises, condenses and falls back under gravity, with no pump. A hot test section degrades the image, so the loop runs at 0.12 bar, where water boils at 50 ◦C, with the heater 1.7 m away and nothing ferromagnetic near the magnet. A steady-state pressure balance model set the pipe diameter and the sizing of the heater, the condenser and the expansion vessel that fixes the pressure of the loop. The loop was built and operated on eleven days, at charges between 48 and 70 percent of its volume. The circulation had two states. A freshly charged loop circulates quickly and unsteadily at 170 mL min−1 to 230 mL min−1, and after roughly four hours it changes, with no way back, to a slow and steady 12 mL min−1. Both states repeat across days, but the change between them is governed by the time since charging rather than by any setting, and its cause is not resolved. The model describes only the slow state. The result is a working thermosyphon whose measurement section can go inside a scanner. The fast state is the one with liquid structures worth imaging, but it drifts throughout and the model does not describe it, so the condition being imaged would not be known. In the slow state, which is steady and predictable, no liquid film is visible in the section at all. The changes needed before a scan can be planned are identified.