Reduction of Conducted Interference by Steel Armor in Buried Cables

Measurements and Modeling

More Info
expand_more
Publication Year
2008
Copyright
© 2008 IEEE
Related content
Reuse Rights

Other than for strictly personal use, it is not permitted to download, forward or distribute the text or part of it, without the consent of the author(s) and/or copyright holder(s), unless the work is under an open content license such as Creative Commons.

Abstract

Switched-mode power supplies in variable-frequency drives often combine good electrical efficiency with generous production of conducted emission. The common-mode (CM) current through the output-to-motor cablemay perturb nearby systems via cable-to-cable crosstalk. Parameters relevant for the coupling are the rise–fall times and amplitude of the output current and voltage, and types and lengths of the cables. Of the many techniques to reduce the crosstalk, we investigated a particular one: reduction of the CM current by the armor of the motor cable. The armor is intended for mechanical protection, but may also substantially reduce the crosstalk. In an actual installation, we measured the transient current through the three phase leads of a motor cable. The cable length was 85 m, and it was buried in wet soil for most of its length. We also measured the transfer impedance of the armor up to 10 MHz, and used this to calculate the overall CM current in a coupled cable model using assumed reasonable values for the cable and soil parameters.Measurements and model results agreed well on the amplitude of the dominant resonance at about 300 kHz. The ratio of the inside transients to CMcurrent was a factor of 20.

Files

Steenstra2008.pdf
(pdf | 0.582 Mb)
License info not available