Whole building HVAC diagnostic Bayesian networks for comfort-related fault detection and diagnosis

Application, evaluation and operational testing

Journal Article (2026)
Author(s)

Martín Mosteiro-Romero (TU Delft - Civil Engineering & Geosciences)

Ziao Wang (TU Delft - Architecture and the Built Environment)

Arie Taal (De Haagse Hogeschool)

Chujie Lu (TU Delft - Architecture and the Built Environment)

Laure Itard (TU Delft - Architecture and the Built Environment)

Research Group
Water Systems Engineering
DOI related publication
https://doi.org/10.1016/j.buildenv.2026.115265 Final published version
More Info
expand_more
Publication Year
2026
Language
English
Research Group
Water Systems Engineering
Journal title
Building and Environment
Volume number
305
Article number
115265
Page Views
33
Reuse Rights

Other than for strictly personal use, it is not permitted to download, forward or distribute the text or part of it, without the consent of the author(s) and/or copyright holder(s), unless the work is under an open content license such as Creative Commons.

Abstract

Automated fault detection and diagnosis (FDD) can support building energy performance and predictive maintenance by leveraging the vast amounts of data generated by building management systems. However, most work on FDD for HVAC systems focuses on individual components, neglecting complex system interactions and the cascading effects of component faults. Diagnostic Bayesian Networks (DBN) offer a particularly promising approach for whole-building FDD due to their robustness, flexibility and scalability. This paper presents the development of a DBN for whole-HVAC FDD and its application in an office building in the Netherlands. The DBN uses aggregated representations of all major building systems to detect which faulty components need further investigation and uses knowledge-based and data-driven methods for parameter estimation. The DBN's performance and the effects of input parameter assumptions are assessed using historical data as well as experimental data obtained by introducing simultaneous faults into the air handling unit (AHU) controls. Although fault injection was restricted to AHU controls due to safety concerns, the model architecture represents all major HVAC systems and simultaneously diagnoses their faults. The results using historical data identified persistent sensor-related anomalies in the building, as well as possibly associated system and control faults. Despite these sensor issues, the evaluation using experimental data showed that the DBN achieved a classification rate of 87.8% for AHU faults while maintaining a low false alarm rate (3.8%). However, the miss rate was high, exceeding 25% in all cases. Finally, the DBN is demonstrated through its application to diagnose a suspected fault during operation.