Experimental and numerical study on earthquake-fire coupling failure mechanism of steel cylindrical tanks

Journal Article (2024)
Author(s)

Jinkun Men (Katholieke Universiteit Leuven, Guangdong Provincial Science and Technology Collaborative Innovation Center for Work Safety, South China University of Technology)

Guohua Chen (Guangdong Provincial Science and Technology Collaborative Innovation Center for Work Safety, South China University of Technology)

Genserik Reniers (Katholieke Universiteit Leuven, TU Delft - Safety and Security Science, Universiteit Antwerpen)

Yue Wu (Guangdong Provincial Science and Technology Collaborative Innovation Center for Work Safety, South China University of Technology)

Hailing Huang (South China University of Technology, Guangdong Provincial Science and Technology Collaborative Innovation Center for Work Safety)

Safety and Security Science
DOI related publication
https://doi.org/10.1016/j.ress.2024.110016
More Info
expand_more
Publication Year
2024
Language
English
Safety and Security Science
Volume number
245
Reuse Rights

Other than for strictly personal use, it is not permitted to download, forward or distribute the text or part of it, without the consent of the author(s) and/or copyright holder(s), unless the work is under an open content license such as Creative Commons.

Abstract

An earthquake-triggered fire domino scenario (E-FDS) is an example of a typical multi-hazard coupling event. The seismic damage can affect the fire resistance of engineering structures, leading to significant mutually amplified phenomena. In this work, a two-stage experimental program is designed to expound the earthquake-fire coupling failure mechanism of steel cylindrical tanks (SCTs). Quasi-static tests are adopted to simulate the damage characteristics of SCTs under seismic excitation (Stage I). Fire tests are adopted to investigate the fire-resistance performance of pre-damaged SCTs (Stage II). The influences of seismic damage on the fire resistance of SCTs are particularly of interest. Three potential seismic damage degrees are considered. The experimental results show that tank specimens exhibit typical diamond-shaped buckling after Stage I. The coupling failure analysis of SCTs is conducted through sequential thermodynamic coupling simulations. Due to factors such as geometric deformation, residual stress, and thermal radiation absorption capacity, the fire resistance of SCTs is significantly attenuated by seismic damage. For the three damage states, fire resistance time attenuation coefficients (0.868, 0.716, 0.511) and critical temperature attenuation coefficients (0.910, 0.779, 0.672) were obtained. This work provides pivotal insights into the mutually amplified phenomena in E-FDSs.

Files

1-s2.0-S0951832024000917-main.... (pdf)
(pdf | 28.5 Mb)
- Embargo expired in 13-08-2024
License info not available