Print Email Facebook Twitter Ramp sinusoidal breakdown of epoxy resin under high voltage waveforms at different frequencies Title Ramp sinusoidal breakdown of epoxy resin under high voltage waveforms at different frequencies Author Zhao, W. (TU Delft High Voltage Technology Group) Luo, T. (TU Delft High Voltage Technology Group) Ghaffarian Niasar, M. (TU Delft High Voltage Technology Group) Date 2021 Abstract In this study, the immediate time to breakdown for pure epoxy resin is measured by applying a ramp sinusoidal voltage signal at certain frequency (50Hz, 500Hz and 5000Hz) until breakdown occurs. The HV testing procedures, epoxy resin sample and experimental set-up preparation and Weibull analysis of obtained results are elaborated. The experiments were carried out on epoxy samples with the thickness between 0.1mm and 0.2mm and the thickness was divided into three groups for more accurate statistical analysis. To reference this document use: http://resolver.tudelft.nl/uuid:9b8d1816-bb99-4e23-8815-9821a479d452 DOI https://doi.org/10.1049/icp.2022.0291 Embargo date 2023-07-01 ISBN 978-1-83953-605-2 Source 22nd International Symposium on High Voltage Engineering (ISH 2021), 2021 (15) Bibliographical note Green Open Access added to TU Delft Institutional Repository ‘You share, we take care!’ – Taverne project https://www.openaccess.nl/en/you-share-we-take-care Otherwise as indicated in the copyright section: the publisher is the copyright holder of this work and the author uses the Dutch legislation to make this work public. Part of collection Institutional Repository Document type conference paper Rights © 2021 W. Zhao, T. Luo, M. Ghaffarian Niasar Files PDF Ramp_sinusoidal_breakdown ... encies.pdf 3.21 MB Close viewer /islandora/object/uuid:9b8d1816-bb99-4e23-8815-9821a479d452/datastream/OBJ/view