Searched for: +
(1 - 5 of 5)
document
Wu, J. (author), Smit, J.J. (author), Mor, A. R. (author)
In practice, High-voltage (HV) cables are occasionally exposed to impulse and superimposed transient conditions, which may initiate partial discharges (PD) temporarily. Whether such PDs persist under AC voltage after the transient conditions have vanished, is at focus in the research described in this paper. Since for cross-linked polyethylene ...
journal article 2020
document
Purnomoadi, A.P. (author), Mor, A. R. (author), Smit, J.J. (author)
This article contains the development of the Health Index (HI) and the Risk Assessment (RA) models for Gas Insulated Switchgear (GIS) operating under tropical conditions. A case study of 631 bays of GIS in tropics with service time from 1 up to 30 years is used during the development of the models. The basis for the HI model is the condition...
journal article 2019
document
Wu, J. (author), Mor, A. R. (author), van Nes, P.V.M. (author), Smit, J.J. (author)
A partial discharge (PD) measuring system has been deployed in order to identify and measure PD in a high voltage (HV) cable joint under impulse and superimposed voltages under laboratory conditions. The challenge is to enable the detection of PD during the impulse conditions. The method of measurement has been investigated by introducing an...
journal article 2019
document
Wu, J. (author), Mor, A. R. (author), Smit, J.J. (author)
In practice, cross-linked polyethylene (XLPE) power cables can be subjected to alternating voltage with superimposed impulse transients. Such impulse transients may initiate partial discharges (PD) in insulation defects even below AC inception voltage. An initiated PD may persist under AC, which will cause insulation degradation. This paper...
journal article 2019
document
Purnomoadi, A.P. (author), Mor, A. R. (author), Smit, J.J. (author)
Humid insulating gas (SF6) has been observed in a case study of 631 CB-bays of Gas Insulated Switchgear (GIS) operating under tropical conditions. The routine gas quality check in the case study reported that 20% of the non-Circuit Breaker enclosures have humidity above the value recommended by the IEEE and IEC standards. Therefore, an...
journal article 2019
Searched for: +
(1 - 5 of 5)