Differential Protection Malfunction due to Transformer Inrush-Induced Harmonics
Hardware-in-the-Loop Simulation Case Study Using RTDS to Optimize Relay Configuration
On 19 December 2021, a single-line fault during energisation occurred in a grid segment in the Netherlands, which was caused by a defective earther fault that failed to disengage. During the fault, the implemented differential protection scheme failed to operate as intended, resu
...