Under-Frequency Load Shedding in Mongolia

Simulation Assessment Considering Inertia Scenarios

Conference Paper (2020)
Author(s)

Choidorj Adiyabazar (National Dispatching Center Co. Ltd )

Martha N. Acosta (Autonomous University of Nuevo León)

Francisco M. Gonzalez-Longatt (University of South-Eastern Norway)

José Luis Rueda Rueda (TU Delft - Intelligent Electrical Power Grids)

P. Palensky (TU Delft - Intelligent Electrical Power Grids)

Research Group
Intelligent Electrical Power Grids
Copyright
© 2020 Choidorj Adiyabazar, Martha N. Acosta, F. Gonzalez-Longatt, José L. Rueda, P. Palensky
DOI related publication
https://doi.org/10.1109/ISIE45063.2020.9152584
More Info
expand_more
Publication Year
2020
Language
English
Copyright
© 2020 Choidorj Adiyabazar, Martha N. Acosta, F. Gonzalez-Longatt, José L. Rueda, P. Palensky
Research Group
Intelligent Electrical Power Grids
Pages (from-to)
1256-1261
ISBN (print)
978-1-7281-5636-1
ISBN (electronic)
978-1-7281-5635-4
Reuse Rights

Other than for strictly personal use, it is not permitted to download, forward or distribute the text or part of it, without the consent of the author(s) and/or copyright holder(s), unless the work is under an open content license such as Creative Commons.

Abstract

Mongolia power system (MPS) is evolving quite fast, and the integration of renewable resources (mainly wind power and solar photovoltaic) reached 20% by 2019. The MPS is interconnected to Russia in order to cover local energy deficits, especially during freezing winters. However, the interconnection to Russia is a sensible element of the MPS, especially from the frequency control and stability point of view. This situation was evident during the sudden disconnection of the two interconnecting lines that provoked the major event of 29th June 2018, disconnecting 112 MW by the action of the Under-Frequency Load Shedding (UFLS) and making more than 1.5 million without electricity that day. This paper is dedicated to using numerical time-domain simulations to assess the existing UFLS schemes installed in the MPS. As the MPS is especially sensitive to disconnection from the Russian grid, this event is used to assess the suitability of the UFLS considering two scenarios: Summer and Winter. Results of this research paper have demonstrated that the actual UFLS scheme is not enough to avoid frequency collapse in real-life conditions during the Summer low-demand and low inertia scenario.