Baseline Study of Ultra-Clean Air Change Rate, Number, and Type of Microorganisms and Level of Particles During Trauma Surgery

Journal Article (2024)
Author(s)

J.L.A. Lans (TU Delft - Environmental & Climate Design)

Nina M.C. Mathijssen (Reinier Haga Orthopedic Center, Reinier de Graaf Gasthuis)

P. R. Goswami (Reinier de Graaf Gasthuis)

J.J. Van Den Dobbelsteen (TU Delft - Medical Instruments & Bio-Inspired Technology)

PG Luscuere (TU Delft - Environmental & Climate Design)

M. Van der Elst (Reinier de Graaf Gasthuis, TU Delft - Medical Instruments & Bio-Inspired Technology)

Research Group
Environmental & Climate Design
DOI related publication
https://doi.org/10.1177/19375867241302406
More Info
expand_more
Publication Year
2024
Language
English
Research Group
Environmental & Climate Design
Issue number
1
Volume number
18
Pages (from-to)
142-156
Reuse Rights

Other than for strictly personal use, it is not permitted to download, forward or distribute the text or part of it, without the consent of the author(s) and/or copyright holder(s), unless the work is under an open content license such as Creative Commons.

Abstract

Background: The objective of an operating room (OR) ultra-clean ventilation system is to eliminate or reduce the quantity of dust particles and colony-forming units per cubic meter of air (CFU/m3). To achieve this, ultra-clean goal high air change rates per hour are required to reduce the particle load and number of CFU/m3. Aim: To determine the air quality in an ultra-clean OR during surgery, in terms of the number and type of microorganism and quantity of dust particles in order to establish a benchmark. Methods: Number of CFUs and the quantity of dust particles were measured. For measuring the CFUs, sterile extraction hoses were positioned at the incision, the furthest away positioned instrument table, and the periphery. At these locations, air was extracted to determine the quantity of dust particles. Findings: The number of CFU/m3 and particles was on average at wound level ≤1 CFU/m3 resp. 852.679 particles, at instrument table ≤1 CFU/m3 resp. 3.797 particles and in the periphery ≤8 CFU/m3, resp. 4.355 particles. Conclusion: The number of CFUs in the ultra-clean area is below the defined ultra-clean level of ≤10 CFU/m3 for ultra-clean surgery. The quantity of dust particles measured during surgery was higher than the defined ISO 5.