HVDC GIS Magnetic Field Antenna System Characterization

Master Thesis (2020)
Author(s)

A.V. Nayak (TU Delft - Electrical Engineering, Mathematics and Computer Science)

Contributor(s)

Armando Mor – Mentor (TU Delft - DC systems, Energy conversion & Storage)

F. A. Muñoz – Mentor (TU Delft - DC systems, Energy conversion & Storage)

L. C. Castro – Mentor (TU Delft - ESP LAB)

Peter Vaessen – Coach (TU Delft - DC systems, Energy conversion & Storage)

Faculty
Electrical Engineering, Mathematics and Computer Science
Copyright
© 2020 Avinash Nayak
More Info
expand_more
Publication Year
2020
Language
English
Copyright
© 2020 Avinash Nayak
Graduation Date
27-08-2020
Awarding Institution
Delft University of Technology
Programme
['Electrical Engineering | Sustainable Energy Technology']
Faculty
Electrical Engineering, Mathematics and Computer Science
Reuse Rights

Other than for strictly personal use, it is not permitted to download, forward or distribute the text or part of it, without the consent of the author(s) and/or copyright holder(s), unless the work is under an open content license such as Creative Commons.

Abstract

Partial Discharge (PD) measurements are of great importance to enable
the monitoring and diagnostics of HV systems. The requirements of the Paris
Agreement and climate goals have fuelled the increase in penetration and demand
of HVDC for offshore wind. The HVDC Gas Insulated Switchgear (HVDC GIS) is a
reliable technology to support the necessary electrical infrastructure.
Nevertheless, some in-service failures may occur. These failures can occur in
the insulation system and thus developing a measurement system for PD detection
is essential for monitoring and diagnostics. To monitor and diagnose the HVDC
GIS, a novel Magnetic Antenna (MA) is being developed to operate in the
high-frequency (HF) (30-300 MHz) range. The well-established UHF method for the
GIS is typically used due to its high sensitivity and resilience to
electromagnetic interference. However, the UHF method is unable to calibrate to
apparent charges as this information is in the low frequency (up to 30 MHz)
until HF range. The knowledge of charge calibration indicates the discharge
type which is important in DC as DC does not have phase-resolved information as
with AC. The appropriate frequency range of the MA should enable the
measurements of the apparent charge and localize the defects when monitoring
and diagnosing a HVDC GIS setup. The overarching goal is to develop a
measurement system to measure PDs in the HF range in a GIS setup. For this
purpose, MAs are created and investigated. A workbench has been built and
developed to characterize the MAs and measure its frequency characteristics. A
380 kV GIS measurement setup has been developed. This enabled the measurement
and acquisition of data of the discharges using the MAs. The Threshold Peak
detection (TPD), Energy Criterion (EC), and Phase Method (PM) localization
methods are investigated and implemented for localization of the source of
defects. The PM is unable to localize the pulse due to its sensitivity to noise
and reflections. The TPD and EC are both suitable with the TPD being the
preferred method due to its 95% accuracy of localizing the defect within ± 1.5
m.   



Files

AVNayak_Master_Thesis_HVDC_GIS... (pdf)
(pdf | 6.75 Mb)
- Embargo expired in 27-09-2022
License info not available