A. Rodrigo Mor
Please Note
68 records found
1
This paper introduces a directional coupler for partial discharge (PD) measurements in gas-insulated substations (GIS). The sensor comprises a combination of magnetic and electric couplers, effectively segregating forward and backward pulses to enhance PD charge estimation and defect location. The sensor's design was supported with finite element method simulations and measurements conducted in a transverse electromagnetic test bench. Comparative analyses were performed against independent magnetic and electric couplers. The charge estimation and the directional coupler's directivity were evaluated in both the test bench and a full-scale GIS with different PD defects. Initially, the combined magnetic and the electric couplers exhibited undesired interactions, prompting corrective measures. Subsequent adjustments included changes to the electric coupler material and modifications to the magnetic coupler construction. The resulting high-voltage directional coupler performed better than the separated couplers in a GIS with discontinuities. This partial discharge sensor emerges as a candidate for future SF6-free alternative GIS.
A degaussing system can be used to reduce the detectability of the magnetic signature of a ship. Commonly, a degaussing system consists of a set of onboard copper coils that produce a magnetic field to compensate for the magnetic signature. High-temperature superconductive degaussing coils are considered an alternative to copper degaussing coils because of a reduction in energy losses, weight, volume, and costs. The losses of a high-temperature superconductor (HTS) degaussing system can be reduced even further by powering it with a cryocooled converter with parallel mosfets. A low-duty cycle and smaller current leads can be used. These solutions eliminate most of the power source losses. This article investigates such a cryocooled converter. The effect of the low switching frequency on the converter performance is tested. A prototype that can operate at cryogenic temperatures was built. The converter powers an HTS coil. It was found that a load current of 50 A can be achieved with a duty cycle of just 0.025 at an input voltage of 3.5 V while still meeting the requirement of a maximum current ripple of 0.5%. At a switching frequency higher than 100 Hz, the converter's performance deteriorates. Also, oscillations were observed in the circuit. This is a problem due to the low blocking voltage of the mosfets. The parasitic inductances in the circuit have a high impact on the performance because the resistance in the circuit is very low.
SF6 is being phased out of the electrical grid as it is a strong greenhouse gas. A 'green' alternative to SF6 is fluoronitrile (C4-FN). The dutch transmission system operator (TSO) TenneT wanted to investigate the electrical behavior of this 'green' alternative as a pilot-gas insulated line (GIL) filled with C4-FN/CO2 (5%/95%) experienced multiple electrical breakdowns during the site acceptance tests (SATs). TenneT hypothesized that the breakdown was caused by the effect of (too much) humidity in the gas. Therefore, the ac breakdown behavior of the gas mixture has been researched under different amounts of humidity and operating pressures. This article also makes a small introduction on how humidity affects partial discharge (PD) behavior of corona, which is often a breakdown indicator. The results of this research conclude that humidity affects the ac breakdown strength. An increase in humidity in the gas results in a decrease in the ac breakdown strength. Moreover, the field configuration determines the amplitude of the impact. The impact of humidity on the ac breakdown strength in a homogenous field is substantially more compared to an inhomogeneous field, where the impact can almost be ignored. Yet, the effect of humidity decreases as the operating pressure increases. The phase-resolved PD pattern and PD characteristics of corona in a C4-FN gas mixture also differ with humidity. On the other hand, the PD inception voltage did not change with the humidity content. As a result of the findings in this research, further research is proposed toward the affected breakdown mechanism and more various PD behavior.
Magnetic and electric antennas synergy for partial discharge measurements in gas-insulated substations
Power flow and reflection suppression
One of the main difficulties in measuring partial discharges (PD) in gas-insulated substations (GIS) is the overlapping of pulses at the sensor's location, which distorts the pulse resolution and the charge estimation. This research presents a new method called “synergy,” which identifies and suppresses reflections using magnetic and electric antennas in the very-high frequency range. By scaling the antennas’ outputs and adding them, it is possible to segregate forward and backward pulses. Additionally, by multiplying the electric and magnetic signals, the power flow of the pulses is obtained, which identifies the propagation direction and the location of discontinuities in the transmission path. The synergy method is evaluated in three scenarios: a fully matched test bench using a calibrated pulse, a full-scale GIS using a calibrated pulse, and a full-scale GIS using a PD defect. The results showed that the pulse reflections can be eliminated from the incident pulse, improving the charge calculation when the pulses overlap. The output of this research represents an improvement for PD monitoring in GIS, exhibiting a tool for better defect localization, pulse wave shape construction, charge estimation, and possible interference rejection.
The insulation condition of HVDC grids consisting of cable systems, GIS, and converters should be monitored by partial discharge (PD) analysers using artificial intelligence (AI) tools for efficient insulation diagnosis. Although there are many experiences of PD monitoring solutions developed for the supervision of the insulation condition of HVAC grids using PD analysers, there are no standardised requirements for their qualification available yet. The international technical specification TS IEC 62478 provides general rules for PD measurements using electromagnetic methods but does not define performance requirements for qualification tests. HVDC and HVAC PD analysers must be tested by unambiguous test procedures. This paper compiles experiences of using PD analysers with HFCT sensors in HVAC grids (cable systems, GIS, and AIS) to define a qualification procedure for HVAC systems. This procedure is applicable to HVDC grids (cable systems, GIS, AIS, and converters) because the particularities related to the insulation behaviour under HVDC voltage are also considered. Representative PD sources are discussed in HVAC and HVDC positive and negative polarity. The PD pulse trend of representative insulation defects in HVDC cable systems is quite different from that of HVAC grids. Special attention should be paid to the acquisition of PD signals in HVDC grids since few pulses appear in solid insulations, mainly during voltage changes (polarity reversals or surges), but rarely in continuous operation with constant direct voltage. A synthetic PD simulator has been developed to reproduce trains of PD pulses or noise signals, similar to those that can appear in the power network. A set of three functionality tests has been developed for qualification of the diagnostic capabilities of PD analysers working up to 30 MHz addressed to HVDC or HVAC grids: (1) PD recognition test, (2) PD clustering test, and (3) PD location test. This qualification procedure has been validated by means of a round-robin test performed by five research institutes (RISE, FFII, TUDelft, TAU, and UPM) using commercial and in-development AI PD recognition and clustering tools to demonstrate its robustness and applicability. Applying this qualification procedure, two PD methods for electrical detection and prevention of insulation defects have been approved, one for HVAC and the other for HVDC grids.
On-site partial discharge (PD) measurements have turned out to be a very efficient technique for determining the insulation condition in high-voltage electrical grids (AIS, cable systems, GIS, HVDC converters, etc.); however, there is not any standardised procedure for determining the performances of PD measuring systems. In on-line and on-site PD measurements, high-frequency current transformers (HFCTs) are commonly used as sensors as they allow for monitoring over long distances in high-voltage installations. To ensure the required performances, a metrological qualification of the PD analysers by applying an evaluation procedure is necessary. A novel evaluation procedure was established to specify the quantities to be measured (electrical charge and PD repetition rate) and to describe the evaluation tests considering the measured influence parameters: noise, charge amplitude, pulse width and time interval between consecutive pulses. This procedure was applied to different types of PD analysers used for off-line measurements, sporadic on-line measurements and continuous PD monitoring. The procedure was validated in a round-robin test involving two metrological institutes (RISE from Sweden and FFII from Spain) and three universities (TUDelft from the Netherlands, TAU from Finland and UPM from Spain). With this round-robin test, the effectiveness of the proposed qualification procedure for discriminating between efficient and inappropriate PD analysers was demonstrated. Furthermore, it was shown that the PD charge quantity can be properly determined for on-line measurements and continuous monitoring by integrating the pulse signals acquired with HFCT sensors. In this case, these sensors must have a flat frequency spectrum in the range between several tens of kHz and at least two tens of MHz, where the frequency pulse content is more significant. The proposed qualification procedure can be useful for improving the future versions of the technical specification TS IEC 62478 and the standard IEC 60270.
There are no accepted procedures that quantify the apparent charge of partial discharge (PD) in gas-insulated substations (GIS). This paper proposes a calibration method for PD charge estimation using unconventional electromagnetic sensors: a magnetic loop antenna (inductive coupler) and an electric antenna (capacitive coupler.) The calibration procedure is intended for the voltage double integral method, which is reviewed for magnetic antennas and extended for electric antennas. By injecting low-frequency sinusoidal signals, the calibration constants are determined for two different test setups: the first one being a testbench where the characteristic impedance is matched and the second one a full-scale 420 kV GIS. The calibration method is validated in three ways: with a calibrated pulse in the testbench, a calibrated pulse in a full-scale GIS, and PD defects in the full-scale GIS. The calibration procedure revealed a frequency limit range dependent on the GIS length and the sensor's signal-to-noise ratio. The three validation methods showed low charge estimation errors for the magnetic and electric antennas, demonstrating that the PD calibration method applies to any electric/magnetic detector with a low-frequency derivative response. This research paves the way for better GIS insulation monitoring and PD sensor harmonization.
Detection of the magnetic signature of ships can be avoided by using a degaussing system; a set of on-board copper coils that compensates for the magnetic signature. High temperature superconductors (HTS) are currently investigated as a replacement for copper degaussing coils. By using HTS, we have to deal with higher currents and therefore with higher power supply losses. Also, large current leads are needed which introduces extra losses. This paper investigates different possible solutions to minimize these losses. Four H-bridge-based MOSFET topologies are presented that were designed to reduce the power supply and current lead losses. The first topology uses an H-bridge configuration so that the degaussing current can freewheel through the low-resistance MOSFETs. The second topology places the H-bridge inside the cryostat so that the current leads can be made smaller. The third topology includes a smoothing capacitor in the cryostat so that the current leads and input current are even smaller. The fourth topology uses a transformer so that the current leads can be eliminated. Measurements were done to determine the MOSFETs and capacitor performance in liquid nitrogen. The simulated losses of the four topologies are compared to determine the most energy-efficient option for supplying current to the HTS coils. It was found that by submerging multiple parallel MOSFETs in liquid nitrogen, the on-state resistance is decreased and the current supply can be made more efficient. Also, by placing a smoothing capacitor inside the cryostat, the current lead losses can be minimized significantly. The benefits of using a transformer do not outweigh the transformer losses.
Space charges are one of the main challenges facing the constantly increasing use of extruded high voltage direct current (HVDC) cables. The Pulsed Electro-Acoustic (PEA) method is one of the most common procedures for space charge measurements of insulation. One issue with the PEA method is distortion due to the crosstalk between the applied voltage pulse and the acoustic sensor. This work analyzed two factors involved in the reduction in this distortion: the influence of the exposed semiconductor distance between the injection electrodes and PEA test cell, and the influence of adding a reactance at the grounding circuit of the PEA test cell. The interaction of these two factors with the distortion was analyzed through a series of experimental testing. Moreover, the performance regarding distortion after applying a developed coaxial injection was compared with the standard non-coaxial injection configuration. It was observed that these two factors had a direct impact on distortion and can be utilized for the reduction in distortion arising from the crosstalk of the applied pulsed voltage. The results can be utilized for the consideration of practical aspects during the construction of a PEA test setup for the measurement of full-size HVDC cables.
A recent investigation explored a new measuring concept used in partial discharges (PD) measurements in gas insulated substations (GIS), consisting of a magnetic loop antenna. The sensor's frequency response was characterized up to some tens of MHz. This paper proposes an improved version of the sensor with an extended bandwidth (BW) one order of magnitude higher: a resonance, attributed to a common mode current in the mounting hole, is identified and eliminated employing ferrite beads in the feeder cables. Moreover, this publication proposes an electric circuit model that fully covers the transverse electromagnetic mode (TEM) frequency range in GIS. The electric model is compared against experimental measurements using a 1 GHz bandwidth testbench, giving accurate results. Two contributions are achieved in this research: an improved magnetic loop antenna with extended bandwidth and an accurate electric circuit model. This publication paves the way for further research on time resolution and signal postprocessing techniques for magnetic loop antennas in GIS.