Capital and operational expenditures of different operating room air-handling installations with conventional or ultra-clean air supply systems

Journal Article (2023)
Author(s)

J. L.A. Lans (Reinier de Graaf Gasthuis, TU Delft - Environmental & Climate Design)

Nina Mathijssen (Reinier de Graaf Gasthuis)

A.A.L. Traversari (TNO)

I. M. Jacobs (Sweegers en de Bruijn)

J. J. van Den Dobbelsteen (TU Delft - Medical Instruments & Bio-Inspired Technology)

Maarten van der Elst (Reinier de Graaf Gasthuis, TU Delft - Support Biomechanical Engineering)

P. G. Luscuere (TU Delft - Environmental & Climate Design)

Research Group
Environmental & Climate Design
Copyright
© 2023 J.L.A. Lans, N. M.C. Mathijssen, A. A.L. Traversari, I. M. Jacobs, J.J. van den Dobbelsteen, M. van der Elst, P Luscuere
DOI related publication
https://doi.org/10.1016/j.jobe.2023.107714
More Info
expand_more
Publication Year
2023
Language
English
Copyright
© 2023 J.L.A. Lans, N. M.C. Mathijssen, A. A.L. Traversari, I. M. Jacobs, J.J. van den Dobbelsteen, M. van der Elst, P Luscuere
Research Group
Environmental & Climate Design
Volume number
78
Reuse Rights

Other than for strictly personal use, it is not permitted to download, forward or distribute the text or part of it, without the consent of the author(s) and/or copyright holder(s), unless the work is under an open content license such as Creative Commons.

Abstract

When making a decision on the operating room air handling installation and type of air supply system, it is relevant to know the expenditures of the different air handling installations and air supply systems. The aim of this study was to determine the capital and operational expenditures of air handling installations equipped with an ultra-clean or with a conventional system. To compare the technical requirements of Dutch air handling installations with European standards and guidelines, and evaluate the costs of surgical site infections in comparison with the capital expenditures. This study fills a gap in knowledge, detailed technical information and costs of air handling installations and air supply systems from multiple completed projects of 24 hospitals were collected, analyzed and compared. Per OR capital expenditures increase by €62,491 to €139,018 when an air handling installation with an ultra-clean system is compared to a conventional system, which is 3%–7% of the total construction costs of a completely new OR department. The yearly increase in operational expenditures per OR with an ultra-clean system compared to a conventional system was €673 to €1,896. The capital and operational expenditures of air handling installations with an ultra-clean system are higher than those with a conventional system. The technical specifications of the ORs studied in the Netherlands correspond to European standards and guidelines. When the impact on patient suffering and costs associated with surgical site infections are weighed against the investment required for an air handling installation with an ultra-clean system, it is worth considering.