Detection of series arcs using load side voltage drop for protection of low voltage DC Systems

Journal Article (2018)
Author(s)

Aditya Shekhar (TU Delft - Electrical Engineering, Mathematics and Computer Science)

Laura Ramírez-Elizondo (TU Delft - Electrical Engineering, Mathematics and Computer Science)

Soumya Bandyopadhyay (TU Delft - Electrical Engineering, Mathematics and Computer Science)

Laurens Mackay (TU Delft - Electrical Engineering, Mathematics and Computer Science)

Pavol Bauera (TU Delft - Electrical Engineering, Mathematics and Computer Science)

Research Group
DC systems, Energy conversion & Storage
DOI related publication
https://doi.org/10.1109/TSG.2017.2707438 Final published version
More Info
expand_more
Publication Year
2018
Language
English
Research Group
DC systems, Energy conversion & Storage
Issue number
6
Volume number
9
Article number
7932971
Pages (from-to)
6288-6297
Downloads counter
330
Collections
Institutional Repository
Reuse Rights

Other than for strictly personal use, it is not permitted to download, forward or distribute the text or part of it, without the consent of the author(s) and/or copyright holder(s), unless the work is under an open content license such as Creative Commons.

Abstract

Low voltage dc distribution grids face issues associated with arc faults, aggravated by the absence of current zero crossing. The focus of this paper is to comprehensively develop a method of series arc fault detection at the load side power electronics, based on the electrode dependent initial voltage drop occurring at the arc initiation. The proposed arc detection algorithm is described along with the structure and time constants of the designed bandpass filter. The operational boundaries of the arc detection algorithm are defined for copper electrodes depending on the set threshold voltage and the system parameters, like grid inductance, resistance, and the load capacitance. Further, the detection time and the zone of guaranteed positive detection are depicted. These are validated through test simulations on the state space model of the system. Finally, experimental validation of the proposed scheme is carried out, wherein, a series arc is generated in the dc circuit and the programmed micro-controller provides a real time signal upon detecting the arcing event. The results on variation in detection time with set threshold voltage are also presented experimentally.